Knowledge Base Article #151 - HU Test Ramping Higher Than Expected on Instantaneous Test
DateApr 9, 2007
ByENOSERV
Filed UnderRTS
ClassGeneral
 
Issue Addressed
 
Causes of Issue
Winding 1 set to 8.7 so it should be calculating to 87 amps but instead is ramping to 104.
 
Solution to this Issue
The stop value entered in Action Specs is set to 120% of expected pickup, hence 104.4 amps. By reducing this to 103% it should result in allowing the test to ramp to 89.6 amps, close to the limit of the Manta MTS-5000.

Another option would be to hookup to a different winding with a lower tap, maybe Winding 2. Then look in the Global Defines and change the formula to calculate based off of WDG_TAP2 rather than WDG_TAP1.