| Knowledge Base Article #189 - Action SOURCE other than PHASE has been selected with MTA_TST! Test will be Aborted! |
|---|
| Date | Feb 23, 2012 |
| By | Robertson, Gina |
| Filed Under | Routine |
| Class | Issue |
| |
| Issue Addressed |
|---|
When running the Sync Angle tests for the 300 series SEL relays, users would receive this message: "Action SOURCE other than PHASE has been selected with MTA_TST! Test will be Aborted!" This affected users of RTS 5.1.1.5 or higher.
|
| |
| Causes of Issue |
|---|
| A code change created a conflict, causing the message to appear. |
| |
| Solution to this Issue |
|---|
We have opted to correct the individual routines.
Solution 1: Modify existing Library Routine
� Open the SEL routine located in the Library side of the Routine Selection window
� Scroll to the bottom on the list and located the following two test procedures. The following change should be made to both tests.
o 25ANG1 SYNC ANGLE (25A1)
o 25ANG2 SYNC ANGLE (25A2)
� Select the User Options Tab
� Select the Advanced Options button
� Scroll to the bottom of the window
� Add the following variable to the last line of the displayed text
o VA_RAMP=0
� This will fix the problem
Solution 2: Download the latest RTS FasData database and merge the following routines into their database
� SEL-300G.FST Version 3.9
� SEL-311B.FST Version 3.9
� SEL-311C.FST Version 3.11
� SEL-351.FST Version 3.9
� SEL-531A.FST Version 3.9
� SEL-351R.FST Version 3.9
� SEL-351S.FST Version 3.10
� SEL-352.FST Version 2.7
|